4268BC TB

Product Details

Manufacturer:
Manufacturer part number:
4268BC
CBT Inventory
0
Vendor Inventory
Loading...
CBT - CINCINNATI
0
CBT - SPRINGBORO
0
CBT - SIDNEY
0
CBT - LEXINGTON
0
CBT - LOUISVILLE
0
Availability:
Ships in 5-7 days.
Estimated dates are contingent upon manufacturer stock.

Description

Type

Russellstoll Hazardous-Duty Plugs, Receptacles and Interlocks

Description

Delayed Reaction Plug, 60 Amp, 3 Pole 4 Wire, 480V, Ratings Type DA, Cable Hole Diameter: 1 1/4 Inch

Application

For use in hazardous materials environment like: Gas or Vapor, Dust, or Fibers/Flyings

Standards

UL e10919

Features

Circuit-breaking receptacles, plugs and connectors ensure complete circuit breaking under full rated loads. Equipment grounding is provided by means of a separate pole that makes contact before and breaks contact after the circuit poles. The delayed action operation sequence is as follows: Insert plug, turn left push in to make electrical contact then turn right to prevent accidental disconnection. To withdraw plug, the reverse procedure is followed, which provides time for extinction of the arc and cooling before the plug can be completely withdrawn

Specifications

Amperage Rating:60 Amps
Country of Origin:US
Harmonized Code:8536694020
Material:Steel and aluminum, natural finish housing
Number of Poles:3
Number of Wires:4
Voltage Rating:480 V

Resources