MPDB67111 FER

Product Details

Manufacturer:
Manufacturer part number:
MPDB67111
CBT Inventory
4
Vendor Inventory
Loading...
CBT - CINCINNATI
0
CBT - SPRINGBORO
0
CBT - SIDNEY
4
CBT - LEXINGTON
0
CBT - LOUISVILLE
0
Availability:
4 in stock
Estimated dates are contingent upon manufacturer stock.

Description

Brand Name

Mersen

Type

Intermediate Open Style

Description

The next generation power distribution block (PDB). Mersen power distribution blocks provide a safe and easy method of splicing cables, splitting primary power into secondary circuits and fulfilling requirements for fixed junction tap-off points. Unless noted otherwise, all blocks are UL and CSA approved while meeting spacing requirements for feeder and branch circuits in conjunction with UL 508 A and the national electric code. PDB options include single or dual conductor primary inputs and up to 30 secondary outputs. Specialty blocks are available allowing for up to 7 primary inputs.
Mersen Power Distribution Block, Intermediate Open Style, Series: MPDB, 600 VAC, 175 A, 1 Pole, 1 Primary Connections/Pole, 12 Secondary Connection/Pole, 14 to 2/0 AWG Line, 14 to 10 AWG Load Wire, 100 kA Short Circuit, Polycarbonate, TiN Coated, Black, 1.85 in W x 5 in D x 3.88 in H Dimensions

Application

Cable Splicing, Splitting Primary Power into Secondary Circuits, Fixed Junction and Tap-Off Point Applications

Standards

RoHS Compliant | UL 1953 File No. E352417 | CSA Class 6228-01

Features

  • Adder poles can be stacked to form multi-pole units in the field without the use of tools, adder poles allow for customization of primary and secondary wire combinations
  • Aluminum connectors accept both aluminum or copper wire while copper connectors accept copper wire only and all 1-piece tin plated
  • Insulators are virtually unbreakable, made of glass filled polycarbonate, see-through hinged safety covers are optional and provide a greater degree of safety and shock resistance where required, hinged covers can be installed without tools
  • 1 in through air and 2 in over surface between uninsulated live parts of opposite polarity meets requirements for feeder and branch circuit applications of UL508A
  • Polycarbonate safety covers provide dead-front protection
  • Each cover has a test probe hole in the center for circuit checking
  • Tin plated aluminum contact
  • One cover is needed for each pole

Specifications

Amperage Rating:175 A
Color:Black
Country of Origin:MX
Dimensions:1.85 in W x 5 in D x 3.88 in H
Finish:TiN Coated
Material:Polycarbonate
Number of Poles:1
Primary Connections/Pole:1
Secondary Connection/Pole:12
Series:MPDB
Short Circuit Current Rating:100 kA
Voltage Rating:600 VAC
Wire Size:14 to 2/0 AWG Line, 14 to 10 AWG Load