Description

Brand Name

Mersen

Description

The Surge-Trap® type 1 STXP series offers advanced performance and features over the STXR series including higher surge capacity and phase LED status indicators. The STXP meets requirements for UL1449 Fourth Edition and has been designed for additional mounting flexibility including mounting feet and flush mount capability. The STXP features TPMOV® technology inside making it the safest product available. Installation can be done on the line or load side of a panel. The STXP is the perfect fit from service entrance all the way down to an important machine specific control panel.
Mersen Surge Protective Device, Series: STXP, 208Y/120 VAC Electrical Rating, 50/60 Hz Frequency, 4 Wires, 200 kA Short Circuit, 100 kA Peak Surge Current, 20 kA Nominal Discharge, Modes of Protection: L-G/L-L/L-N/N-G, LED/Remote Audible Alarm Indicator, 3 ph, Environmental Conditions: -40 to 85 deg C Operating Temperature, -40 to 85 deg C Storage Temperature, NEMA 4X Enclosure, Panel/Wall Mounting, Pre-Wire Terminal, Aluminum/Polycarbonate, 3.13 in W Dimensions

Application

For indoor/outdoor and type 1 or 2 SPD applications

Standards

RoHS Compliant | ANSI/UL 1449 File No. E210793 | CSA C22.2 Class 9091-02 File No. 162842 | ANSI/IEEE C62.41.1, C62.41.2, C62.45 | UL96A | UL94-5VA Flammability Rating

Features

  • Designed with the industry leading MERSEN TPMOV® technology (internally fused)
  • Enhanced 100 kA surge capacity for longer life and higher single impulse withstand
  • LED status indicator (ON = Good, OFF = Replace) LED phase loss indicators (ON = Operational, OFF = maintenance Required)
  • NEMA 4X enclosure for outdoor or indoor use
  • Mounting hub and mounting feet for installation flexibility
  • Pre-wired with 3 ft leads for easy installation

Specifications

Country of Origin:MX
Dimensions:3.13 in W
Electrical Ratings:208Y/120 VAC
Enclosure Type:NEMA 4X
Environmental Conditions:-40 to 85 deg C Operating Temperature, -40 to 85 deg C Storage Temperature
Frequency Rating:50/60 Hz
Indicator Type:LED/Remote Audible Alarm
Material:Aluminum/Polycarbonate
Modes of Protection:L-G/L-L/L-N/N-G
Mounting Type:Panel/Wall
Nominal Discharge Current:20 kA
Number of Wires:4
Peak Surge Current:100 kA
Phase:3
Series:STXP
Short Circuit Current Rating:200 kA
Terminal Type:Pre-Wire